Question

How should equipment be marked with new Type of Protection designations be handled in accordance with IEC 60079-14?

Interpretation

Equipment marked with new Type of Protection designations shall be applied in accordance with IEC 60079-14 requirements based on the following points and IEC 60079-14:2013, Table 2

• Ex “eb” should be treated as equivalent to Ex “e”

• Ex “ec” should be treated as equivalent to Ex “nA”

• Ex “db” should be treated as equivalent to Ex “d”

• Ex “dc” requirements should be based on Ex “d” requirements but is only suitable for EPL Gc

• Ex “ob” should be treated as equivalent to Ex “o”

• Ex “oc” requirements should be based on Ex “o” requirements but is only suitable for EPL Gc

Source: https://www.iec.ch